Autoswitcher AS2000DR is fitted inside feeder pillar.
q
The electric load to be connected to the unit should not
exceed 5A (Resistive) at 230V/50 Hz. Since
the load in practical applications is never pure resistive, it should not exceed
2.5 A for general lighting load like incandescent bulbs or fluorescent tubes.
This factor of safety is essential considering the starting surge
currents.
q
If the load current is more than the specified, it is
advisable to use contactor. The
unit can drive the contactor of any rating.
q
A fuse of 5A should be placed in series with the output
cable to avoid the accidental short. The unit does not have built-in fuse.
It should be clearly understood, in the event of overload or short, the
unit will be damaged if no external fuse is provided.
q
Placement of sensor is to be done very judiciously.
It should be preferably placed horizontally and outdoors sensing the
ambient light only. It should not
receive the light from the connected load.
q
The “TWILIGHT” setting is factory-calibrated at 16 to
20 lux which is satisfactory for a normal dusk-to-dawn operation assuming the
sensor is properly placed. In case
a different setting is desired, adjust the “TWILIGHT” control towards (+)
for early on or (-) for late on operations.
It must be noticed that there is a limit to adjust this setting to the
extreme ends. If it is taken to
extreme negative end to switch the light at maximum darkness, even a slight
light from the connected load may switch off the load when on after the delay
time. Similarly, connected load
will be continuously on if it is taken to maximum positive side. Once this
setting is done, it should not be disturbed ever.
Also, it is to be understood the unit is tracking the set ambient light
and not the time of the day for its on/off action.
WIRING
DETAILS:
q
The output of the unit is potential-
free contacts and hence load to be connected can be of AC or DC of any voltage
upto 440V AC.
q
For the normal 230V-operated load, pin
1 (MAINS ‘0’) and pin 4 (OUTPUT) are to be used as output to get mains
supply to load while pin 2 (MAINS ‘230’) and pin 3(OUTPUT) are permanently
shorted with suitable wire.
|
MAINS |
OUTPUT |
SENSOR |
||||||
|
|
|